A virtual instrument for diagnosis to substation grounding grids in harsh electromagnetic environment

Publication Type:
Conference Proceeding
Citation:
I2MTC 2017 - 2017 IEEE International Instrumentation and Measurement Technology Conference, Proceedings, 2017
Issue Date:
2017-07-05
Filename Description Size
07969925.pdfPublished version927.72 kB
Adobe PDF
Full metadata record
© 2017 IEEE. To improve the traditional electromagnetic induction methods for grounding grid diagnosis, a virtual instrument is proposed to detect weak signals in the harsh and noisy substation electromagnetic environment. The induced electric signal in the coil of wire, containing multi-source and intense noises, is collected by the NI DAQ device. Then virtual phase intensive detectors and digital filters constitute the lock-in amplifier to suppress noise. In the experimental test, a small model of grounding grid is diagnosed in a man-made break situation. The visualized result shows the feasibility and accuracy of the proposed virtual instrument.